Ideal for offices, servers, networking equipment, medical equipment, security systems and industrial applications, this UPS provides dependable backup power while helping protect connected equipment from voltage fluctuations, surges and electrical disturbances.
High frequency on-line double conversion technology
DSP (Digital signal processors) control technology
Active power factor correction (APFC), input power factor up to 0.99
Output power factor 0.9/1.0
Wide input voltage range (110 V ~ 300 Vac) and frequency range (40 ~ 70 Hz)
Auto sensing frequency
50 / 60 Hz frequency conversion
Cold start
Rear ventilation design and variable speed fan
Effective software and hardware protection
Quick and stable charging, 90% capacity restored in 3h (standard model UPS)
Linear derating in low voltage input reducing battery discharging times
Settable delayed start when power is restored
Advanced battery management (ABM)
Multiple functions settable via LCD: output voltage, EOD, auto-start, bypass mode
Multi-platform communications: RS232 (standard), USB / RS485 / SNMP / dry contacts (optional)
Optional USB, RS485 card, AS400 dry contacts, SNMP card, SMS alarms, EPO function
Technical Specifications
| MODEL | AE 1 KVA | AE 2 KVA | AE 3 KVA | ||||||||||||||||||||||
| Capacity | 1 kVA / 1 kW | 2 kVA / 2 kW | 3 kVA / 3 kW | ||||||||||||||||||||||
| Rated voltage | 208 / 220 / 230 / 240 Vac | ||||||||||||||||||||||||
| Voltage range | 110 -176 Vac ( linear derating beMeen 50% and 100% load ); 176 -280 Vac (no derating); 280 – 300 Vac (derating 50%) | ||||||||||||||||||||||||
| Frequency | 50/60 Hz + 5 Hz (auto-sensing) | ||||||||||||||||||||||||
| Power factor | 0.95 | 20.99 | |||||||||||||||||||||||
| Bypass voltage range | – 40% – +20% (settable) | ||||||||||||||||||||||||
| Rated input frequency | 50 Hz / 60 Hz (auto-sense) | ||||||||||||||||||||||||
| THDi | s 5% | ||||||||||||||||||||||||
| Voltage | 208 / 220 / 230 / 240 Vac (settable via LCD) | ||||||||||||||||||||||||
| Voltage regulation | +1% | ||||||||||||||||||||||||
| Frequency | 45 – 55 Hz or 55 – 65 Hz (synchronized range); 50 / 60 Hz + 0.1 Hz (battery mode) | ||||||||||||||||||||||||
| Waveform | Sinusoidal | ||||||||||||||||||||||||
| Power factor | 1.0 | ||||||||||||||||||||||||
| THDv | s 2% (Iinear load), s 5% (non-Iinea r load) | ||||||||||||||||||||||||
| Crest factor | 3:1 | ||||||||||||||||||||||||
| Overload | 105% – 110% for 30 min , 110% – 130% for 10 min , 130% – 150% for 30s, > 150% for 500 ms | ||||||||||||||||||||||||
| Battery type | Sealed lead acid maintenance free battery | ||||||||||||||||||||||||
| DC voltage | 24V(S) | 24V(H) | 36V(S) | 36V(H) | 48V(S) | 48V(H) | 72V(S) | 72V(H) | 72V(S) | 72V(H) | 96V(S) | 96V(H) | |||||||||||||
| Inbuilt battery | 2•9Ah | / | 3 7Ah | 4 9 Ah | / | 6 7 Ah | 6 9 Ah | / | 8 7 Ah | ||||||||||||||||
| Cha rging current (max.) | 12 A (1 -12A settable) | ||||||||||||||||||||||||
| Recharge time | Standard model: 90% capacity restored in 3 hours; Long time model: depend on the capacity of battery | ||||||||||||||||||||||||
| Efficiency | |||||||||||||||||||||||||
| (Bat encode) | (Bat encode) | (Bat e mode) | (Batt 2” ode) | (Batt 2” ode) | % (Bat e mode) | ||||||||||||||||||||
| * 98.5% (ECO mode) | * 98.5% (ECO mode) | * 99% (ECO mode) | * 99% (ECO mode) | * 99% (ECO mode) | * 99% (ECO mode) | ||||||||||||||||||||
| Transfer time | Mains mode to battery mode: 0 ms Inverter mode to bypass mode: 4 ms (typical) | ||||||||||||||||||||||||
| Protections | Short-circuit, overload, overtemperature, battery discharge protection and fan testing protection | ||||||||||||||||||||||||
| Communication port | RS232 (standard), US B / RS485 / SNMP/ dry contacts (optional) | ||||||||||||||||||||||||
| Display | LCD + LED | ||||||||||||||||||||||||
| Operating humidity | 0 – 95 % RH @ 0 – 40°C (non-condensing) | ||||||||||||||||||||||||
| Storage temperature | -25° C – 55°C (excl ude batteries) | ||||||||||||||||||||||||
| Operating altitude | 1000m, above 1000m, derating 1% for each additional 100 m | ||||||||||||||||||||||||
| IP rating | IP 20 | ||||||||||||||||||||||||
| Noise level at 1m | s 50 dB | ||||||||||||||||||||||||
| Dimensions (W D H) (mm) | 144 312 216 | 144 x312 •216 | 144 x371 216 | 144 x312 216 | 144 x417 •216 | 144 x417 216 | 191 x419 335 | 144 x417 •216 | 191 x419 335 | 144 x417 •216 | 191 419 335 | 144 x417 •216 | |||||||||||||
| Packaged dimensions (W D x H) (mm) | 230 402 315 | 230 •402 •315 | 230 460 •315 | 230 x402 •315 | 230 x506 315 | 230 506 315 | 277 500 435 | 230 •506 •315 | 277 x500 •435 | 230 x506 •315 | 277 500 435 | 230 x506 •315 | |||||||||||||
| N et weight (kg) | 8.8 | 4.0 | 10.9 | 4.0 | 15.9 | 6.1 | 21.4 | 6.1 | 23.8 | 6.5 | 25.6 | 6.5 | |||||||||||||
| Gross weight (kg) | 9.8 | 5.1 | 12.1 | 5.1 | 17.3 | 7.5 | 23.1 | 7.5 | 25.6 | 8.0 | 27.3 | 8.0 | |||||||||||||